Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM02579
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/28/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE PROPER CONNECTOR FOR DISHWASHER AND DISPOSAL CORDS WHERE THEY ENTER APPLIANCE - NEC 400.3 2. PANEL FOR UNIT #1 HAS GROUND BAR THAT IS MISSING FACTORY SCREW THAT CONNECTS BAR TO CAN AND NEUTRAL. SELF TAPPING SCREW NOT ALLOWED -- NEC 110 & 250 3. I COULD NOT OPEN PANEL DEAD FRONT COVER FOR PANEL #2 - SCREW RAN INTO TIGHT. |
|
| 07/26/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CORD FOR DISPOSAL TO LONG -- NEC 422.16 B1 2. CORD FOR DISHWASHER TO LONG -- NEC 422.16 B2 3. ALL SWITCHES NEED TO BE GROUNDED -- NEC 404.9 B 4. AT SERVICE PANEL, DO NOT INSTALL NEUTRAL AND EQUIPMENT GROUND UNDER SAME SET SCREW AND CAN'T HAVE DIFFERENT SIZE EQUIPMENT GROUNDS UNDER SAME SET SCREW -- NEC 110 & PANEL CABLE 5. TIGHTEN ALL LOOSE DEVICES -- NEC 404.10, NEC 406.4 |