Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM02578
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/30/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/30/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. NO TEST ON ABS 2. WHO GAVE PERMISSION TO INSULATE? NO PORTION OF ANY WORK MAY BE CONCEALED UNTIL IT HAS BEEN INSPECTED AND APPROVED. |
|
| 05/25/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. ALL PIPING REQUIRES SUPPORT. 2. HORIZONTAL ABS OVERHEAD REQUIRES SUPPORT. 3. TUB WASTE WET 4. HORIZ. X HORIZ. CHANGE OF DIRECTION TO BE A SWEEP. 5. SCREW CLOSET FLANGES TO FLOOR TO BE INSTALLED CORRECTLY. 6. TEST ABS THRU ROOF. 7. SUPPORT TRAP ARMS AS CLOSE TO 90 DEGREES AS POSSIBLE. |