Permit: T06CM02576

Parcel: 14118001H

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T06CM02576

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/11/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) CHECKED FIRE WRAP
2) ELIMINATE UNNECESSARY OFF SETS IN WATER HEATER VENT. EXTEND 2' ABOVE PARAPET WALL
3) LEFT GAS CARD. DO NOT TURN GAS ON TO WATER HEATER
4) OK FOR CEILING TILES
05/04/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO FIRE WRAP GREASE DUCTS
ON FINAL BE SURE DUCT SMOKE DETECTORS HAVE AUDIBLE AND VISIBLE ALARMS & ALARM FOR DUCT DETECTOR FAILURE.
CONDENSATE PIPING OK TO INSULATE IF REQUIRED.