Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T06CM02576
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/11/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) CHECKED FIRE WRAP 2) ELIMINATE UNNECESSARY OFF SETS IN WATER HEATER VENT. EXTEND 2' ABOVE PARAPET WALL 3) LEFT GAS CARD. DO NOT TURN GAS ON TO WATER HEATER 4) OK FOR CEILING TILES |
|
05/04/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO FIRE WRAP GREASE DUCTS ON FINAL BE SURE DUCT SMOKE DETECTORS HAVE AUDIBLE AND VISIBLE ALARMS & ALARM FOR DUCT DETECTOR FAILURE. CONDENSATE PIPING OK TO INSULATE IF REQUIRED. |