Permit: T06CM02573

Parcel: 108203200


Addresses:

4162 N FORTUNE LP

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
01/04/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
OK FOR SHEETROCK
12/06/2006 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE KITCHEN EXHAUST.
DO NOT USE INSERT FITTINGS ON CONDENSATE DRAIN.
2ND FLOOR EXHAUST FAN MISSING DAMPER.
11/07/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
CK. WATER HTR. B-1 VENT PIPE PENETRATING 2X6 FRAMED WALL. NEED ADDN. CLEARANCE IN CENTER OF WALL (PENETRATION)