Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/03/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE ITEMS 5 & 7 FROM PREVIOUS INSPECTIONS 2. OTHER INSPECTION ITEMS CORRECTED |
|
| 03/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIX RECEPTACLE IN GARAGE-INSTALL PLATE 2) FRONT OUTDOOR RECEPTACLE NOT GFI PROTECTED AND INSTALL COVER PROPERLY 3) SMOKE DETECTOR AT ENTRY MOVED-CANNOT HIDE BOX ABOVE SHEETROCK CEILING 4) INSTALL SWITCH PLATE 2ND FLOOR BATHROOM 5) NEED 6" CLEARANCE TO SHELF STORAGE AREA FROM RECESSED FIXTURE 2ND FLOOR BEDROOMS 6) BACK OUTDOOR RECEPTACLE VERY LOOSE 7) NEED ROOF ACCESS TO CHECK ROOF TOP UNIT 8) RECALL WHEN READY |