Permit: T06CM02546

Parcel: 141095720

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/05/2007 FRAMING Approved IVRS - Inspection :*
01/23/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 1, 3, 5 & 6 FROM 1/16/07 NOT DONE CORRECTLY
01/22/2007 FRAMING Not ready for Inspection IVRS - Inspection :*
1) NOT READY PER JIM
01/16/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHEARWALL REPAIR MUST HAVE 2 X BACKING AND EDGE NAIL ALL EDGES
2) NO GAS TEST
3) DUCT KINKED IN POWDER ROOM
4) PROVIDE 2 X POST PER NOTE 6 AT LR GLB
5) 1" CLEARANCE REQUIRED AT B-VENT
6) FIRE STOP STAIR
7) NEED ENGINEERING REPAIR POST TENSION ISLAND CUT APPROVED BY CITY OF TUCSON
8) NAIL PROTECT WASHER DRAIN
01/10/2007 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) NO GAS TEST
2) GARAGE SHEARWALL HAS 10" X 20" UNAUTHORIZED HOLE. REPAIR
3) DUCT FOR LIVING ROOM BY POWDER ROOM HAS TOO SHARP OF BEND-1 DUCT DIAMETER MINIMUM
4) POST TENSION SLAB CUT IN KITCHEN. YOU MUST PROVIDE A CITY APPROVED POST TENSION ENGINEERS REPAIR. DO NOT REPAIR WITHOUT CITY INSPECTION FOR REPAIR COMPLIANCE
5) PVC CONDUIT FOR ISLAND MUST HAVE MINIMUM 2" CONCRETE COVER
6) STOPPED INSPECTION-TOO MANY ITEMS