Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM02546
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/05/2007 | FRAMING | Approved | IVRS - Inspection :* | |
01/23/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 1, 3, 5 & 6 FROM 1/16/07 NOT DONE CORRECTLY |
|
01/22/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER JIM |
|
01/16/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHEARWALL REPAIR MUST HAVE 2 X BACKING AND EDGE NAIL ALL EDGES 2) NO GAS TEST 3) DUCT KINKED IN POWDER ROOM 4) PROVIDE 2 X POST PER NOTE 6 AT LR GLB 5) 1" CLEARANCE REQUIRED AT B-VENT 6) FIRE STOP STAIR 7) NEED ENGINEERING REPAIR POST TENSION ISLAND CUT APPROVED BY CITY OF TUCSON 8) NAIL PROTECT WASHER DRAIN |
|
01/10/2007 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) NO GAS TEST 2) GARAGE SHEARWALL HAS 10" X 20" UNAUTHORIZED HOLE. REPAIR 3) DUCT FOR LIVING ROOM BY POWDER ROOM HAS TOO SHARP OF BEND-1 DUCT DIAMETER MINIMUM 4) POST TENSION SLAB CUT IN KITCHEN. YOU MUST PROVIDE A CITY APPROVED POST TENSION ENGINEERS REPAIR. DO NOT REPAIR WITHOUT CITY INSPECTION FOR REPAIR COMPLIANCE 5) PVC CONDUIT FOR ISLAND MUST HAVE MINIMUM 2" CONCRETE COVER 6) STOPPED INSPECTION-TOO MANY ITEMS |