Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM02539
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/29/2006 | ELECTRIC - FINAL | Approved | GROUNDING SYSTEM INSTALLED & CONNECTED TO BOTH DISCONNECTS. NOTE: MULTIPLE LUGGING ON LINE SIDE PREVIOUSLY OK PER C.CLEMENS 6/21/06 |
|
06/21/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED TO INSTALL GROUNDING ELECTRODE SYSTEM FOR SERVICE AND CONNECT TO BOTH SERVICE DISCONNECTS 2 GROUND RODS NO CLOSER THAN 6' APART WOULD BE ACCEPTABLE. CHARLIE 349-5029 ALL ELSE OK |
|
06/08/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. GROUNDING ELECTRODE TO SERVICE HAS BEEN CUT 2. CORRECTLY IDENTIFY PANEL DIRECTORY. 3. SAFE OFF ALL OPEN WIRING (HOLES IN BOXES AND COVERS) 4. THERE IS NO EMERGENCY/EXIT LIGHTING 5. SECURE ALL DEVICES SO THEY ARE NOT LOOSE. 6. SECURE OPEN RUNS OF ROMEX. 7. COOLING SYSTEM NOT OPERATING. |