Permit: T06CM02539

Parcel: 113100050


Addresses:

2743 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM02539

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/29/2006 ELECTRIC - FINAL Approved GROUNDING SYSTEM INSTALLED & CONNECTED TO BOTH DISCONNECTS.
NOTE: MULTIPLE LUGGING ON LINE SIDE PREVIOUSLY OK PER C.CLEMENS 6/21/06
06/21/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEED TO INSTALL GROUNDING ELECTRODE SYSTEM FOR SERVICE AND CONNECT TO BOTH SERVICE DISCONNECTS
2 GROUND RODS NO CLOSER THAN 6' APART WOULD BE ACCEPTABLE. CHARLIE 349-5029
ALL ELSE OK
06/08/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. GROUNDING ELECTRODE TO SERVICE HAS BEEN CUT
2. CORRECTLY IDENTIFY PANEL DIRECTORY.
3. SAFE OFF ALL OPEN WIRING (HOLES IN BOXES AND COVERS)
4. THERE IS NO EMERGENCY/EXIT LIGHTING
5. SECURE ALL DEVICES SO THEY ARE NOT LOOSE.
6. SECURE OPEN RUNS OF ROMEX.
7. COOLING SYSTEM NOT OPERATING.