Permit: T06CM02528

Parcel: 136087850


Addresses:

9650 E 22ND ST


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM02528

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/29/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
09/21/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. COMPLETE LIST FROM 9/18/06
09/18/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- SAFETY PLATES MISSING
- HB STUB DAMAGED
- PLAN SPECS CALL FOR PIPE LABELS
09/13/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO INSULATE AND LABEL PIPING AS SPECIFIED ON PLAN.
SUPPORT HORIZONTAL PVC VENT - INSTALL TWO HANGERS.
SECURE 4" VENT FROM MOVING IN WALL,
REMOVE BURNED AND MELTED SECTIONS OF VENT PIPING.
INSTALL SAFETY PLATES
CORRECT SLOPE ON T&P DRAIN
HORIZONTAL CHANGES OF DIRECTION ON TRAP ARM SHALL BE MADE W/WYE PATTERN FITTINGS.