Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM02528
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/29/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/21/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. COMPLETE LIST FROM 9/18/06 |
|
09/18/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - SAFETY PLATES MISSING - HB STUB DAMAGED - PLAN SPECS CALL FOR PIPE LABELS |
|
09/13/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO INSULATE AND LABEL PIPING AS SPECIFIED ON PLAN. SUPPORT HORIZONTAL PVC VENT - INSTALL TWO HANGERS. SECURE 4" VENT FROM MOVING IN WALL, REMOVE BURNED AND MELTED SECTIONS OF VENT PIPING. INSTALL SAFETY PLATES CORRECT SLOPE ON T&P DRAIN HORIZONTAL CHANGES OF DIRECTION ON TRAP ARM SHALL BE MADE W/WYE PATTERN FITTINGS. |