Permit: T06CM02521

Parcel: 141153570

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM02521

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/07/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/06/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. WE HAVE BOX OVERFILL ABOVE SWITCHES
2. OUTSIDE EM LIGHT NOT WORKING
12/05/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. CONNECT EM LIGHT FOR OUTSIDE.
2. AN APPROVED EXTENDER RING IS NEEDED FOR BOXES MORE THAN 1/4" FROM BOX TO SURFACES OR FLUSH AT COMBUSTIBLES.
3. FINISH VDV CABELING 725.6
4. LIGHTS TO BE DUAL SWITCHED AS PER PLANS & ENERGY CODES.
5. EXIT LIGHTING TO BE ON AREA SERVED 700.12

OK ROOF
12/04/2006 ELECTRIC - FINAL Cancelled CANCELLED PER RAY OF G & J DEVELOPMENT #240-1596
12/04/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED BY OFFICE