Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM02519

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/17/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/16/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
LABEL PANEL CORRECTLY
08/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ROOFTOP GFI RECEPTACLE HAS NO POWER
2. COMPLETE ITEMS FROM PREVIOUS INSPECTION ON 4/20/07
3. WIRING DOES NOT APPEAR TO BE CORRECT HAVE GROUNDED GFI RECEPTACLES THAT WILL NOT TRIP WHEN TESTED.
05/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
GO OVER LIST VERIFY ALL DONE, NO ONE ON SITE
05/25/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
04/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. ON ROOF: NEED SERVICE RECEPTACLE, NEED PROPER WORKING CLEARANCE IN FRONT OF DISCONNECT, INSTALL FUSES.
2. REMOVE ALL PAINT FROM SUB-PANEL INTERIOR ON WIRING, BREAKERS, CONNECTIONS
3. IDENTIFY PANEL DIRECTORY
4. HAVE DEAD RECEPTACLES, GFI'S NOT TRIPPING, OPEN GROUND ETC.
5. BATH GFI TO BE WITHIN 36" OF SINK
6. CONDENSATE PUMP TO BE ENERGIZED BY RECEPTACLE, NOT CUT CORD END
7. ALL BEDROOM OUTLETS INCLUDES LIGHTS RECEPTACLES AND SMOKE DETECTORS NEED ARC FAULT PROTECTION.
8. KITCHEN COUNTER RECEPTACLES TO BE LOCATED ABOVE COUNTER SURFACES.
9. MAX. LENGTH FOR DISPOSAL CORD IS 36"
10. NEED RANGE INSTALLED AND RECEPTACLE FOR RANGE
11. PROPERLY GROUND FURNACE, INSTALL COVER OPEN J-BOX IN CEILING.