Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM02518
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/28/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE TO6CM03804 |
|
| 08/22/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK COVER EXCEPT J-BOX AREA |
|
| 06/28/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) A CONNECTOR IS NEEDED AT METAL BOXES AND PANEL 2) PROTECT CONDUCTOR FROM SCREWS INSIDE OF BOX 314.43 3) NEW PANEL NOT ALLOWED IN CLOSET. PLANS DO NOT SHOW NEW PANEL. PLEASE REVISE PLANS |