Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/17/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/16/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE A TRAP ON CONDENSATE DRAIN |
|
| 10/12/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - SINGLE WALL FLUE PIPE TOO CLOSE TO COMBUSTIBLE MATERIAL. - UNABLE TO REMOVE FILTER FROM UNIT - REFRIGERATION PIPING INSULATION TOO CLOSE TO FLUE PIPE IT IS COMBUSTIBLE - NO SECONDARY DRAIN ON AC COIL |