Permit: T06CM02506

Parcel: 125110830


Addresses:

3647 E 2ND ST #102


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM02506

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/10/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES MORE THAN 1/4" 314.20 ALSO, FLUSH IN COMBUSTIBLES
2. INSTALL FIXTURES AS PER INSTRUCTIONS
3. GROUND JUNCTION BOX
4. CLEAN EXCESS DIRT FROM PANELS
10/02/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. 2-WIRE RECEPTACLE OR GFI PROTECTION WHERE THERE IS NOT A GROUND
2. GFI NOT TRIPPING/RESETTING
3. INSTALL ALL COVER PLATES
4. IN SUB-PANEL
A. MULTI-WIRE BRANCH CKT'S TO TERMINATE ON
SEPARATE PHASES
B. ONLY SAME SIZE GROUNDS UNDER SAME SCREW ON GROUND BAR
C. NUMBER BREAKERS, DIRECTORY TO BE CORRECTLY MARKED
5. MAX. LENGTH DISPOSAL CORD IS 36"

PARTIAL INSPECTION - GO THROUGH UNIT BEFORE CALLING IN