Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM02506
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES MORE THAN 1/4" 314.20 ALSO, FLUSH IN COMBUSTIBLES 2. INSTALL FIXTURES AS PER INSTRUCTIONS 3. GROUND JUNCTION BOX 4. CLEAN EXCESS DIRT FROM PANELS |
|
| 10/02/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. 2-WIRE RECEPTACLE OR GFI PROTECTION WHERE THERE IS NOT A GROUND 2. GFI NOT TRIPPING/RESETTING 3. INSTALL ALL COVER PLATES 4. IN SUB-PANEL A. MULTI-WIRE BRANCH CKT'S TO TERMINATE ON SEPARATE PHASES B. ONLY SAME SIZE GROUNDS UNDER SAME SCREW ON GROUND BAR C. NUMBER BREAKERS, DIRECTORY TO BE CORRECTLY MARKED 5. MAX. LENGTH DISPOSAL CORD IS 36" PARTIAL INSPECTION - GO THROUGH UNIT BEFORE CALLING IN |