Date Description Inspector Results Comments
05/01/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) 1ST VISIT: NEED $108.00 CHECK
2) BOND SERVICE RISER
3) NEED SEALING TYPE LOCKNUT FOR NIPPLE INTO PANEL AND BRANCH RACEWAY
4) CORRECTLY IDENTIFY PANEL DIRECTORY
5) IDENTIFY WHITE USED AS HOT
-------------------------------------------------------------------------------------------------
1) 2ND VISIT: OK CABLE DROP, 02018
2) $108.00 MONEY ORDER RECEIVED
3) OK PARTIAL FINAL, STILL NEED INSPECTION FOR EXPIRED GAS PACK UNITS PERMIT (T06EL00475) BEFORE THIS PERMIT WILL BE FINALED