Permit: T06CM02483

Parcel: 115155220


Addresses:

819 W CALLE RETAMA

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/11/2006 FRAMING Approved IVRS - Inspection :*
12/04/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HEADER SIZES NOT PER PLAN
2) SHIM BEARING HEADERS, STUDS, ETC...
3) SEAL ALL STAPLE PENETRATIONS INSIDE HOUSE
4) INSTALL BANG PLATES THROUGHOUT ELECTRIC/PLUMBING
5) WINDOWS/DOORS OMITTED
6) SECURE DRYER VENT AND ALSO COMPRESSED TO MUCH
7) NO TEST DWV
8) NEED WORKING TEST POTABLE H20
9) STOPPED INSPECTION-INCOMPLETE