Permit: T06CM02473

Parcel: 122172600

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
10/02/2007 BUILDING - FINAL Approved IVRS - Inspection :*
10/01/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ANSWER AT DOOR
2) NEED ACCESS TO DO INSPECTION
08/31/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED ARC FAULT BREAKERS FOR ALL BEDROOM CIRCUITS
2) CONDENSATE CANNOT DRAIN INTO SEWER VENT
3) SUPPORT DUCT WORK AT VIBRATION COLLARS
4) INSTALL BONDING WIRE JUMPERS ACCROSS VIBRATION COLLARS
5) INSTALL SUB-PANEL NEUTRALS AND GROUNDS TO ABIDE BY SUB-PANEL WIRING STANDARDS