Permit: T06CM02473

Parcel: 122172600

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
05/23/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
05/10/2007 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) OK TO COVER LEDGER CLIPS ONLY
05/04/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) A35'S MISSING ALL LEDGER CONNECTIONS
2) REVISE PLAN TO SHOW TJI 210 12" ON CENTER
3) MISSING CLIPS THROUGHOUT BASE PLATES KING STUDS
4) CLIP ALL HEADERS
5) COMPLETE ALL AS BUILTS
6) CHECK ALL BRACED PANEL NAILING
04/25/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) I-JOISTS NOT PER PLAN
2) POSITIVE CONNECTION LEDGERS TO BEARING
3) INCOMPLETE
4) CANNOT LOCATE AS BUILT PORCH PLAN PER PREVIOUS INSPECTION
5) STOPPED INSPECTION
04/20/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NAILING ON SHEAR PANELS NOT COMPLETE
2) SHEARPANEL ARE SUPPOSE TO BE 4' WIDE
3) HOLDOWN AT S.W. CORNER NOT CONNECTED TO SHEAR PANEL
4) NEED ANCHOR BOLTS AT DOOR OPRNING SOUTHSIDE
5) NEED PROTECTION PLATES ON PLUMBING VENT AT BOTTOM PLATE-SOUTH WALL
6) NEED H2.5 ON KING STUDS AT WINDOW