Permit: T06CM02469

Parcel: 140550760

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/25/2006 FRAMING Approved IVRS - Inspection :*
07/24/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GARAGE #2 SHEARWALL NOT CONNECTED TO TRUSSES PER 6/SD3
2) LEAK AT KITCHEN DWV
3) FIRE BLOCK STAIR
4) MAXIMUM ALOOWED DIFFERENCE IN STAIR RISE 3/8" NOW 1/2"
5) SECOND FLOOR SHEARWALL #6 REQUIRES NAILS AT 6" ON CENTER AT BOTTOM PLATE 16D COMMONS
07/21/2006 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) HOLDOWNS BY SOUTH WALL NOT INSTALLED-NOT NAILED (REPEAT)
2) WATER HEATER T & P LINE REQUIRES NAIL PROTECTION (REPEAT)
3) YOU REQUESTED A GAS LINE INSPECTION BUT YOU HAVE NOT INSTALLED GAS LINE. EITHER INSTALL GAS LINE OR HAVE GAS DELETED FROM PERMIT (REPEAT)
4) GARAGE #2 SHEARWALLS IS NOT CONNECTED TO FLOOR TRUSSES. SEE 6/SD3 AND GENERAL NOTE
5) HOUSE NOT READY-STOPPED INSPECTION
07/20/2006 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) NO CONSTRUCTION GFCI OUTLET ON CIRCUIT BREAKER
2) YOU REQUESTED GAS LINE INSPECTION BUT HAVE NO GAS LINE INSTALLED. YOU MUST EITHER INSTALL GAS LINE OR HAVE 03050 REMOVED FROM YOUR PERMIT
3) NAIL PROTECT T & P LINE
4) HOLDOWNS THAT WERE NOT INSTALLED OR MISSED AT EXTERIOR CLIP ARE STILL NOT INSTALLED. YOU MUST PAY REINSPECTION FEE
5) GARAGE #2 SHEAR WALL IS NOT CONNECTED TO FLOOR TRUSSES
6) STAIRS CANNOT EXCEED 7 3/4" RISE OR 3/8" DIFFERENCE IN RISE
7) STAIR LIGHT MUST BE 6'-8" ABOVE STAIRS
8) TOO MANY ITEMS-STOPPED INSPECTION
07/19/2006 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) WE CANNOT INSPECT INTERMEDIATE INSPECTION UNTIL LATHE IS COMPLETE
2) YOU MUST EITHER HAVE 03050 GAS REMOVED FROM YOUR INSPECTION CARD OR INSTALL GAS LINES PER PLAN