Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/24/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 07/14/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HOLDOWNS ARE NOT INSTALLED 2) NEXT FAILURE WILL BE CHARGED A REINSPECTION FEE |
|
| 07/12/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* | |
| 07/11/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) NO CHANGE 2) NEXT FAILURE WILL REFEE |
|
| 06/30/2006 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* | |
| 06/29/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) ITEMS 1 AND 3 FROM 6/27/06 NOT DONE 2) OK TO DRY IN EXTERIOR |
|
| 06/27/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SOUTH EAST SHEARWALL WEST HOLDOWN WRONG LOCATION CANNOT BE ON CRIPPLES 2) SECOND FLOOR 4040 HEADER NOT CLIPPED. ALSO ALL HEADERS 3) PATIO WEST SIDE HOLDOWN NOT UN-SHEARWALL EAST SIDE 4) SAFETY BRACE REQUIRES 2-16D NAILS ON ENDS 5) OSB MUST SPAN 2 BAYS OR 3 TRUSSES-BLOCK EDGES FRONT LOW ROOF 5) MAIN ROOF OK |