Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM02458
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/18/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/15/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. INSTALL ADDRESS AND UNIT # ON SERVICE 2. IDENTIFY SERVICE DISCONNECT AS "SERVICE DISCONNECT' 3. CRIMPS FOR BONDING CONDUCTORS NOT PROPERLY INSTALLED 4. VERIFY CONNECTION TO EXISTING SERVICE BOND/GROUNDING ELECTRODE. 5. TIGHTEN ALL GROUNDING/BONDING CONNECTIONS. 6. NEED SEALING LOCKNUTS ABOVE LIVE PARTS? 7. TIGHTEN ALL RACEWAY FITTINGS 8. SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE. 9. HAVE TWO DIFFERENT SIZE CONDUCTORS UNDER SAME TERMINATION IN GUTTER. 10. REMOVE "LOOP" ON NEUTRAL @ SUB PANEL 11. EMT NOT ALLOWED FOR SERVICE RISER INTO CAN |
|
08/14/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* SERVICE (NEW) TO BE BONDED TO EXISTING SERVICE GROUNDING ELECTRODE AND PIPE BONDS. |