Permit: T06CM02458

Parcel: 105102410

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM02458

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/18/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/15/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTALL ADDRESS AND UNIT # ON SERVICE
2. IDENTIFY SERVICE DISCONNECT AS "SERVICE DISCONNECT'
3. CRIMPS FOR BONDING CONDUCTORS NOT PROPERLY INSTALLED
4. VERIFY CONNECTION TO EXISTING SERVICE BOND/GROUNDING ELECTRODE.
5. TIGHTEN ALL GROUNDING/BONDING CONNECTIONS.
6. NEED SEALING LOCKNUTS ABOVE LIVE PARTS?
7. TIGHTEN ALL RACEWAY FITTINGS
8. SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE.
9. HAVE TWO DIFFERENT SIZE CONDUCTORS UNDER SAME TERMINATION IN GUTTER.
10. REMOVE "LOOP" ON NEUTRAL @ SUB PANEL
11. EMT NOT ALLOWED FOR SERVICE RISER INTO CAN
08/14/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
SERVICE (NEW) TO BE BONDED TO EXISTING SERVICE GROUNDING ELECTRODE AND PIPE BONDS.