Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/12/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/21/2007 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 06/14/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DO NOT REDUCE THE SIZE OF CONDENSATE DRAIN FAN COILS 2) SECONDARY DRAIN PAN MUST BE 1 1/2" LARGER ON ALL SIDES OF UNIT 3) PROVIDE OVERFLOW SENSOR OR SECONDARY DRAIN 4) PROVIDE ACCESS DOORS FOR FIRE DAMPERS |
|
| 04/03/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SUSPENDED ROUGH DUCT OK TO INSULATE ALL DUCTING |
|
| 03/15/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CHECKED WALK IN COOLER FAN COILS & CONDENSATE DRAINS. OK TO USE. |
|
| 02/21/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CHECKED EVAC. DRAIN SYSTEM OK TO PROCEED. SLOPE IS OK |
|