Inspection History Details
Inspection Status: Partial Approval
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T06CM02412
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/17/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* | |
06/15/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) GW FROM INTERCEPTOR TO TIE IN-OK TO COVER 2) PRODUCE MISTING SYSTEM OK |
|
06/14/2007 | PLUMBING - ROUGH, SOIL | Denied | ||
05/11/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) GREASE INTERCEPTOR INSTALLED PER PLAN, UP STREAM PIPING ONLY 2) OK TO COVER |
|
05/10/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* STARBUCKS DWV W/TEST THRU ROOF AND COPPER OK |
|
05/09/2007 | PLUMBING - ROUGH, SOIL | Cancelled | ||
05/04/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* OK TO COVER PIPING W/DIRT. INSTALL FLOOR SINKS, FDS, CLEANOUT AND PIPE WRAPS RECALL PRIOR TO CONCRETE CORRECT MISSION COUPLING ON VENT IT IS LEAKING AND INSTALLED UPSIDE DOWN. RETEST AND CALL FOR INTERMEDIATE. |
|
04/30/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* DOMESTIC SOIL WASTE IN DELI OK TO COVER CLOSET FLANGES IN PHARMACY TR OK |
|
04/19/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* WASTE PIPING AT SUSHI INSTALLED PER FLOOR PLAN W/FS AT 3 COMP SINK. REDLINE SCHEMATIC DRAWING TO SHOW FS RFI USE OF 3 COMP SINK. USE PERM CAP ON DEMO. |
|
04/03/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* COMB WASTE AT #14 SODA AND AT #9 OK TO COVER INSTALL FCO PROTECT PIPING PASSING THRU CONCRETE |
|
03/22/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* HCS TO TWO-WAY CLEANOUT ON SIDE OF BUILDING TEST OK |
|
03/15/2007 | PLUMBING - ROUGH, SOIL | Cancelled | ||
03/14/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. ROUGH PLUMBING AT FLORAL OK 2. CLEAN OUT HAS A CRACK 3. DWV AT RESTROOMS REQUIRE WATER TEST AND SAFETY PLATES 4. FLUSH-O-METERS AT URINALS REQUIRE HAMMER ARRESTORS. |
|
02/14/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* GW AT SEAFOOD/MEAT DEPT. PER REDLINES ON YELLOW REVISED PLAN DATED 1/31/06 |
|
02/12/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* WATER TEST WASTE & VENT IN SEAFOOD & MEAT PREP PER REDLINE IN TRAILER THRU ROOF. ITEM PLISR AT TRIM STATION COULD REQUIRE A DIRECT DRAINAGE CONNECTION PER ITEM 3 P4 FOR GARBEL UNIT AND A FLOOR SINK DRAINAGE PER ITEM 4 P4 YOUR FLOOR SINK IS NOT INSTALLED AT THIS LOCATION DELEATED BY REDLINE AND INSTALLED CLOSER TO PLHSW VERIFY YOUR NEEDS PLEASE |
|
01/30/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* BREAKROOM SINK ROUGH, PRE-SLAB AND INTERMEDIATE OK VENT CONNECTED TO EXISTING INSTALL SAFETY PLATE CONDENSATE CANNOT CONNECT TO SINK |
|
01/26/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1/2" CW PER PAGE P-2 ITEM 9 IN NOTES FROM EXISTING ABOVE CEILING DOWN IN WALL UNDERGROUND TO CASE. |
|
01/25/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* GW FROM MOP SINK TO MAIN AND FS FOR EVAC SYSTEM OK TO COVER, OK TO POUR CONCRETE STAMPED LETTER FROM ENGINEER ALLOWING 1% FALL ON DRAIN FROM TOILET RMS RECEIVED AND ACCEPTED. |
|
01/18/2007 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
01/17/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* DRAIN FOR DISPOSER IN PRODUCE AREA OK SOIL MAIN IN EAST AREA ADDITION WITH 1/8" PER FOOT SLOPE OK PER AIR SYSTEMS ENGINEERING. |
|
01/08/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* RANDY REQ. AFTER HRS. INSP. PAID W/MONEY ORDER 08-617400922 TOILET RMS, TROUGH DRAINS AND MAIN BETWEEN COLS. 9 AND 10 OK TO COVER SUBJECT TO PLAN REVISION FOR LESS THAN 2% FALL. UNDERGROUND AND ABOVE SLAB W/FIXTURE FITTINGS AND REVENT TESTED TO 10' |
|
01/08/2007 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* BACKPITCH PRESENT AT LAVS AND AT EAST MAIN AND TROUGH DRAIN. ALSO, SUPPORT ALL HORIZONTAL PIPING W/DIRT; TRAP ARMS 4" MAIN INSTALLED AT 1/8" PER FOOT PROVIDE APPROVED PLAN ALLOWING 1% FALL REDLINE FOR CONTINUATION OF PROJECT. OK TO COVER SUBJECT TO PLAN REV. REMOVE GROUT FROM ABS |
|
01/04/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* RANDY 480-390-4263 AFTER HRS. INSP. MONEY ORDER 08 6174 00674 GW FROM COL F.2 TO EXTERIOR A3.5 |