Permit: T06CM02412

Parcel: 13323190A


Addresses:

7812 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM02412

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/28/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/17/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
LAST ITEM -- REVISED AS BUILT PLAN WITH APPROVAL STAMP
3RD PARTY OR CITY
08/15/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OUTSIDE - CAP OFF UNUSED BOX
2. CORDS NOT ALLOWED ABOVE CEILING
3. FINISH GUTTER & CONTROLLER - BACK DOOR
4. NEED VERIFICATION FOR SCREW IN FLEX CONNECTOR FOR OVER 250V
5. FINISH SPEAKER WIRES - 725.6
6. REVISE PLANS AS BUILT AND RESTAMP FOR FINAL

OK ROOF, POWER TO GONDOLAS & LIGHTING, PANEL LABELING
08/14/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK PANEL PD1, P34, P2, "STARBUCKS P2", BD1, BD2

1. PROTECT SEAL TITE FROM SHARP METAL EDGES
2. FILL UNUSED OPENINGS IN GUTTER - BY DOOR
3. CONNECT GROUNDS - BY DOOR
4. CORDS NOT ALLOWED - BEER SIGNS
5. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING
COOKIE AISLE
6. FINISH SPEAKER WIRE
08/13/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. NEED GENERATOR TEST REPORT
2. NEED LABELING FOR GENERATOR 700.8
3. VERIFY IF CONTROL WIRE IS 300V RATED (PIA)
4. FINISH LABELING AS PER 408.4 -- NO ABBREVIATIONS
5. CORRECTLY INSTALL LOCK NUTS
6. VERIFY MULTI-POLE TERMINATIONS AT BREAKERS
08/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
OK CORD DROP SELF
CHECK WRAPS

1. BOX FILL IN HALL
2. FINISH BAKERY/DELI FROM 7/11/07
3. SUPPORT NEW CABLING (VDV) AS PER 725.6
4. PANELS SCHEDULES TO BE AS PER 408.4
07/26/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK COMPACTOR
07/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
COMPACTOR:
1. FINISH BOND BUSHINGS - 250.97
2. CONDUCTORS TO BE COLOR CODED 277/480V - 210.5(C) AMENDMENTS
3. BOND ENCLOSURE

DELI BAKERY/HALL:
1. FINISH ITEMS 1, 2, 3 OF 7/11/07

CORD DROP CASH WRAPS:
1. FINISH ITEMS 1 & 2 OF 7/17/07
07/17/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK CORD DROP OLIVE BAR
OK SUSHI BAR

1. CORD DROP SELF CHECK WRAPS
A. SUPPORT FLEX 300.11
B. GROUND JUNCTION BOX

RECEIVED MONEY ORDER 08-748650391 -- $108.00
07/17/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
COMPACTOR:
1. BOND BUSHING AT CONCENTRICS 250.97
2. TIGHTEN LUGS & LOCKNUTS & MISSING LOCKNUTS
3. CLEAN METAL SHAVINGS IN BOTTOM CONTROL BOX

SUSHI KIOSK
1. GROUND JUNCTION BOX
2. FILL UNUSED OPENINGS
3. GFI'S NOT WORKING
07/12/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
07/11/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. CONDUIT SUPPORTS TO BE EFFECTIVE
2. SEAL ENTRANCE TO WALK-IN AS PER 300.4 BAKERY/DELI
3. SUPPORT M/C 12" BOX - 6' LIGHT

OK LIGHTS MAGAZINE/CARDS
OK FLOOR BOXES
OK LIGHTS BAKERY/DELI
OK CORD DROPS 4
07/03/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK DELI CASE
OK BACK WALL BAKERY
OK DEFROST FAN
OK SODA STATION
OK RECOVERY W/H
OK SODA LIGHTS
OK COSMETIC LIGHTS
06/28/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK 2 DAIRY COFFINS CASES REFRIGERATION PWR
OK DELI ISLAND REFRIGERATION PWR

1. MOUNT BOXES AS PER 314.23 -- NO SCREWS INSIDE

RECEIVED MONEY ORDER #08-741556313 FOR $108.00
06/27/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SUPPORT CONDUITS EXITING CONDUCTORS
2. SEAL FLOOR BOXES FROM WATER EXCLUSIONS

OK ROTISSIERE
OK 2 PLUGS IN CEILING TILE
OK FRONT TO TILE EXCEPT AS NOTED
OK 2 PLUGS BAKERY LINE UP
06/25/2007 ELECTRIC - FINAL Partial Approval 1. FULLY TERMINATE CONDUCTORS AT TRAC'S
2. PROPERLY GROUND LIGHTS DELI - USE TERMINAL END WITH STRANDED CONDUCTORS
3. BOND JUMPER TO BE PER 250.122
4. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 400.8

OK DOORS & FLY FANS (2)
OK TO CLOSE CEILING AT GONDOLA
OK CHEESE TABLE
OK BAKERY OVEN
OK PROOFER

RECEIVED MONEY ORDER 08-741556197 FOR $108.00
06/20/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK DISCONNECT MAIN AIR HANDLER
OK BAKERY COOLER
06/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1. EQUIPMENT BONDING JUMPER TO BE AS PER 250.122
2. MAINTAIN WORKING CLEARANCE OVEN DISCONNECT 110.26
3. IDENTIFY CONDUCTORS CORRECTLY 200.6
06/15/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) GROUND LIGHT FIXTURES
2) DEMO OUT CONDUIT LAYING ON GRID
3) SEAL OPEN CONDUITS
4) SUPPORT SECURITY CAM WIRE IN SOFFIT
06/14/2007 ELECTRIC - FINAL Partial Approval OK TO ENERGIZE EVAP CONDENSOR
RECEIVED CHECK #1008 FOR $108.00
06/12/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK EVAP CONDENSOR CONTROLS TO CROSSOVER

1. VERIFY IS SCREW IN FLEX CONNECTOR GOOD FOR
OVER 250V
06/11/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK SEAFOOD PREP AREA TO USE
OK ROOF OVER NEW AREA

1. SUPPORT MC & FLEX CONDUITS AS PER 300.11
2. TIGHTEN LOOSE FITTINGS
06/08/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
06/07/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK BAKERY AREA AIR HANDLER UNIT
OK 3 FRONT END CASES OK 3 BACK END CASES
06/06/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. ISOLATE PRIMARY CONDUCTOR TO BREAKER INSIDE OF UNIT.
2. SERVICE RECETACLE TO BE LIVE WHEN UNIT IS OFF
3. DOES 440.14 APPLY

OK AIR HANDLER BREAKROOM
06/05/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK BEER CELLAR EAST TO NEW SECTION
OK 1ST DRAFT STOP BACK TO BACK OF STORE
OK M/C CABLES TO JUNCTION BOXES
OK 3 RECEPTACLES COIN-STAR

1. SUPPORT FLEX 300.11
2. TIGHTEN LOOSE FITTINGS
3. CLEAN UP ABOVE CASES AND SECURE CABINET OR REMOVE
05/31/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. GFI WIRED INCORRECTLY
2. DELI OCCUPIED WITHOUT INSPECTIONS COMPLETED
3. NEED CLEARANCE PANEL "BDI"

OK CASH REGISTERS 5-B
05/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. IDENTIFICATION OF IG GROUNDS NOT DONE AS DISCUSSED
2. DELI PREP RECEPTACLES TO BE GFCI
3. PHARMACY SUPPORT OF VDV NOT DONE
05/25/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK STARBUCKS
OK DELI CASES
OK 3 + 3 CASH WRAPS SUBJECT TO REMOVAL OF ABANDONED VDV CABLING 725.3 & 800.3
05/24/2007 ELECTRIC - FINAL Partial Approval 1. OPEN NEUTRAL STARBUCKS
2. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8 PHARMACY
3. FINISH VDV CABELING -- PHARMACY

OK TEMP USAGE OF PHARMACY

RECEIVED MO#08-741535490 $108.00
05/23/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FINISH ALL POWER TO DELI CASE
2. FINISH STARBUCKS KIOSK -- LIGHTS NOT WORKING
CLEARLY LABEL ALL POWER FROM OTHER PANELS.
05/22/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK TO BE INSPECTED NOT READY
05/21/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK BAKERY CASES C-7
OK BATHROOMS

1. USE CORRECT HARDWARE TO HANG ELECTRICAL EQUIPMENT -- NOT DRYWALL SCREWS.
2. FILL UNUSED OPENINGS IN GUTTER

PHARMACY
1. SUPPORT VDV CABLING 725.6, 800.6, 300.11
2. GROUNDING EQUIPMENT CONDUCTORS (ISO) TO BE CORRECTLY COLORED 250.119 ENTIRE LENGTH.
3. PLEASE VERIFY LISTING FOR ORANGE INTERDUCT.
4. PHARMACY IS IN USAGE WITHOUT APPROVAL INSPECTIONS
PLEASE VACATE TO FINISH INSPECTIONS.
05/15/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK PVC DELI SUBJECT TO VERIFICATION OF GLUE WITH CONDUIT.
2. OK SELF CHECK STANDS
3. OK WATER HEATER ABOVE STARBUCKS
05/11/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK CONDUIT RUNS 3/4" AND 1" EMP THROUGH BACK SECTION
2) FINISH SELF CHECK STANDS
05/10/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK BACK 3 ROWS OF LIGHTS TO ENERGIZE
OK TOWER DISCONNECTS
OK WET RACK LAST 48'
OK END CASES & CAP FROZEN 3

SUPPORT VDV CABELING AS PER 300.11
VDV CABLES TO BE SECURE UPON EXITING WALKER DUCT
TIGHTEN CONNECTONS TO WALKER DUCT

1. PROTECT FLEX CONDUIT & VDV CABLES FROM PHYSICAL DAMAGE AT SELF CHECKOUT STANDS.
05/07/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK DELI WALL
OK DELI COOLER UNIT -- NO LIGHTS
OK WALKER DUCT FRONT OF STORE
OK FRONT CANS
OK FRONT ENTRANCE WALL
05/03/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK FROZEN FISH & MEAT CASES
OK CONNECTIONS RACK "D" MAIN

ROOF:
1. BOND BUSHINGS OVER 250V 250.97
2. LABEL DISCONNECTS
3. WE HAVE MULTIPLE TERMINATIONS AT LUGS
4. TIGHTEN LOOSE FITTINGS
05/01/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. ARE BATHROOM RECEPTACLES GFCI PROTECTED 210.8?
2. EXTENDER RINGS MAY BE NEEDED IF MORE THAN 3/4" FROM BOX TO SURFACE.

OK FROM BREAKER TO MAIN LUGS RACK "D"
04/26/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK FINAL 20' OF 4" PVC & 2 2" PVC FROM FRYS BUILDING TO FUTURE GAS STATION
2. OK FINAL ROW OF LIGHTS IN STOCK ROOM
04/23/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. WRAP AND PROTECT WALKER DUCT ADAPTOR PER 300.7
2. NEED TEMP CIRCUIT DIRECTORY FOR STARBUCKS PANEL
3. SUPPORT M/C CABLE FROM "J" BOXES
OK WATER DUCT CONNECTIONS
OK FROZEN FISH & MEAT CASES
OK FROZEN FOOD END CAPS (4)
OK TO COVER CONDUITS PRODUCE WALL
4. SUPPORT JP CABLES & CABLING OR CASH COUNTERS
5. TIGHTEN LOOSE FITTINGS

RECEIVED MONEY ORDER FOR $108.00
04/19/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
04/17/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
PHARMACY
1. 2X4'S TO BE SECURELY ATTACHED TO GRID 410.16
2. TIGHTEN LOOSE M/C CONNECTORS
3. LABEL DISCONNECT
4. FINISH VDV CABELING

PANEL STARBUCKS
1. TIGHTEN TRAPEZE NUTS
2. TIGHTEN LOOSE SET SCREW FITTINGS

OK WALL FOR STARBUCKS PANEL FEEDER
04/13/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
04/12/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SUPPORT VDV CABLING AS PER 725.3 & 6, 800.3 & 6
MEAT SHOP
2. GROUND JUNCTION BOXES WITH DEVICES
3. LABEL CIRCUITS IN DEFROST PANEL 408.4
ALSO, LABEL BREAKERS -- TO BE DONE BY 4/13/07

OK TO ENERGIZE MEAT COOLER, MEAT PREP, PACKAGE DELI
OK TO CLOSE BOXES ABOVE MEAT SHOP
04/11/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FITTINGS STILL LOOSE
2. USE APPROVED STRAPS - NOT PLUMBERS TAPE
3. SUPPORT VDV CABELING 725.6

OK 3/4" PVC EAST WALL OUT
PROMO DISPLAY DAIRY
OK EAST EXTERIOR WALL
04/10/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. LOOSE FITTINGS - FLEX & CONDUIT
2. SUPPORT CONDUITS & FLEX CONDUITS
3. SUPPORT LOW VOLTAGE CONTROL WIRES DOWN WALL
4. MAKE UP INCOMPLETE
5. FILL UNUSED OPENINGS IN BOX -- NOT FITTINGS
6. GROUND JUNCTION BOX
7. CANNOT DISTINGUISH CIRCUITS AT PANEL FOR THIS EQUIPMENT.

RECEIVED MONEY ORDER #08-684789450 $108.00
04/05/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. NEW VDV CABELING TO BE AS PER 300.11
2. TIGHTEN LOOSE FITTINGS
3. CANNOT STACK LUGS - W/H DISCONNECT
4. VERIFY DISCONNECTING MEANS FOR FLY FANS

OK TEMP LIGHTING IN NEW AREA
OK CONDUIT ON RACK FRONT HALF NEW AREA
OK BOXES TO CLOSE BACKROOM

* WILL NEED PLAN REVISIONS FOR W/H CHANGE
04/03/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK PVC CONDUITS OUT TO ISLAND SEAFOOD
OK FLORAL CASES TO USE

1. SUPPORT & PROTECT PVC AT WALL
2. VERIFY BOX FILL FOR DAIRY COOLER LIGHTS (DOOR)
03/26/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
03/25/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/23/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED BY RANDY
03/22/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK 2 NEW MEAT COVERS
1. FILL ALL UNUSED OPENINGS IN BOXES
03/20/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TEMP DAIRY COOLER
OK TEMP END CAP COOLER
OK WALL NEW BATHROOMS
03/19/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BOXES NOT ALLOWED SCREWS IN FRONT PORTION OF BOX 314.23
2. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING

OK DAIRY COOLER CEILING LIGHTING
OK PHARMACY RADIUS - WALL
03/16/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
03/15/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
03/14/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. GROUND LUG TO HAVE FULL SURFACE CONTACT
2. RACEWAYS TO BE CONTINUOUS
3. ISOLATE ENERGIZED CONDUCTORS INSIDE REFRIGERATION UNITS.
4. SEAL FOR INSIDE OF CONDUIT TO BE NON-COMBUSTIBLE.

OK TO ENERGIZE EVAC
OK WALLS SEAFOOD & MEAT ROOM
03/12/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK BAILER
OK PRODUCE PREP COOLERS
03/07/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PREVENT TEMPERATURE DIFFERENCE 300.7 -
PRODUCE PREP
2. BAILER: SUPPORT SEAL TITE, BOND PER 250.97, GROUNDING 250.8, CLEARANCE 110.26

OK 2 - 3/4" PVC FOR PRODUCE ISLAND
OK TO ENERGIZE RECEPTACLES STOCK AREA, RACK B & C
03/06/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK CONDUITS & BOXES ON RACKS & PLUGS IN BACK STOCK ROOMS.
03/01/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
CHILLER:
1. TIGHTEN LOOSE FITTINGS
2. TAP CONTROL SIDE OF DISCONNECT CORRECTLY
NOT MULTI-TAPING OF LUGS

OK GROCERY FREEZER -- LIGHTING ONLY
02/28/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. CHECK CONDUIT SUPPORT WHEN COLUMN IS BUILT
2. FILL UNUSED OPENINGS IN RACK "A"

OK FROZEN 3 & RACK "A" TO ENERGIZE
02/27/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK WATER HEATER ABOVE PRODUCE COOLER
02/26/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PANEL SCHEDULES TO BE EVIDENT TO WHAT SERVED 408.4
2. LABEL WATER HEATER DISCONNECT
3. ONLY ONE CONDUCTOR PER LUG
4. CLEAN SURFACE UNDER LUG
5. MAINTAIN CLEARANCES AT REFRIGERATION CONTROLS

OK BEER LINE UP, FROZEN 1 & 2 TO ENERGIZE
02/23/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
CIRCUIT BREAKERS CHANGED TO 15A AT FOLLOWING PNL PER ENG. LETTER ON DERATION

PBD-2 2, 39, 41
RPA 2, 41
RLA 20, 25, 37, 39
PFA 18, 29, 31
RFA-2 3, 32, 34, 36

OK TO ENERGIZE
02/22/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/16/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SHEETMETAL SCREWS NOT ALLOWED FOR BONDING 250.8
2. FILL UNUSED OPENINGS RACK "B & G"
3. GROUND ENCLOSURE - CABINET CONTROLS
4. ONLY ONE CONDUCTOR PER TERMINAL
02/15/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK CASE WIRING FROZEN #2
02/14/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK CASE WIRING - FROZEN I
02/13/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK CONDUITS TO FROZEN 1 FROM GUTTER
OK CONDUIT 10' UP FROM PANELS BD2, BD1
02/12/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK CONDUIT TO BEER LINE UP
FROM GUTTER
1. PLEASE VERIFY LISTING LABELS FOR COOLERS.
02/11/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
01/31/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CONTRACTOR TO MAINTAIN LOCK OUT/ TAG OUT
2) PANELS AND SERVICES ARE CLEARED AS PER STICKER COMMENTS
01/30/2007 ELECTRIC - FINAL Cancelled CANCELLED BY DALE
01/18/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TEMP USAGE FOR PRODUCE PREP & COOLER