Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM02412
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/17/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
07/12/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* |
|
06/20/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
06/15/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
06/14/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FLORAL: CAP PLUG STIP CONDUCTOR WITH AN APPROVED TERMINATION-NOT BLACK TAPE 2) CORDS NOT ALLOWED FOR PERMANENT WIRING METHODS 400.7 3) WHERE IS DISCONNECTING MEANS FOR ICE MACHINE 4) NEED PERMANENT CIRCUIT DIRECTORIES 5) BONDING JUMPER TO BE SIZED PER 250.122 6) CLEAN SURFACE UNDER GROUND BAR 250.12 7) TILES: OK ICREAM CASE TO COLUMN 4.0 AND COLUMN H BACK, OK FLOOR BOX CHICKEN WARMER-CONDUIT AND BOX AND OK CONNECTION SEAFOOD STEAMER |
|
06/01/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CANS FROM SOFFIT NO LIGHT LEAKS IN HOOD DUCT 1. BOXES IN SLAB COVERED WITHOUT INSPECTION CANNOT BE USED UNTIL INSPECTED RECEIVED MONEY ORDER #08-741555488 FOR $108.00 |
|
05/21/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
05/07/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
05/01/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/30/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TEMP DELI & BAKERY OK END WALL FROZEN SEAFOOD |
|
04/23/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/17/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/13/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SENSOR & SPLICES TO BE ACCESSIBLE OK WALKER DUCT OK HARD LID BATHROOMS EXCEPT AS NOTED OK DEFROST CABINET LABELING |
|
03/26/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK FLORAL WALL 2) OK W/P COVER NEW ROOF-OK TO USE |
|
03/25/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
03/23/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
03/20/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/19/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/16/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS PHARMACY EXCEPT RADIUS OK NEW LIGHTS SEAFOOD OK TO USE NEW ROOF GFCI'S 1. SUPPORT M/C & FIXTURE WHIPS CORRECTLY * W/P COVERS 406.8 |
|
03/15/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUPPORT BOXES INSIDE OF UNITS. 2. TIGHTEN LOOSE FITTINGS. 3. PLEASE VERIFY IF BOX IS FOR BONDING AT 250V OR MORE 250.97 4. FILL UNUSED OPENING 5. MAINTAIN WORKING CLEARANCE REMOTE HEADERS OK TEMP DAIRY/DELI CASES TO ENERGIZE OK TO CONNECT NEW FEEDERS TO RFA2 |
|
03/14/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/12/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/06/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/15/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/14/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/13/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/12/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/11/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TEMP POWER TO NEW SHELL 1. LABEL CIRCUIT DIRECTORIES 2. CUT TIES LOOSE FOR BUNDLING TO PREVENT HEATING OF CONDUCTORS. 3. PLEASE VERIFY DERATING OF CONDUCTORS IN GUTTER AND RACEWAYS. 4. ONLY ONE CONDUCTOR PER TERMINAL GROUND BAR IN GUTTER. 5. OPEN JUNCTION BOXES 6. SUPPORT CONDUIT AS PER CODE - 3' & 10" 7. VERIFY NUMBER OF CONDUCTORS PER WIRE NUT. |
|
02/07/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) AREAS AND EQUIPMENT HAVE BEEN ENERGIZED WITHOUT INSPECTION-PLEASE DE-ENERGIZE UNTIL INSPECTED |
|
02/01/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO PANELS PD1, P3, P3A, BD1 AND BP2 AS MARKED ON STICKERS 2) OK BREAKROOM WALLS |
|
01/29/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* DISCUSSED SERVICE EQUIPMENT WITH CONTRACTOR |
|
01/12/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
01/03/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. JUNCTION BOXES TO BE ACCESSIBLE 2. SCREWS AND NAILS TO BE PER 314.23 (B) (1) 3. SUPPORT CONDUITS OK WALLS PRODUCE PREP |
|
12/13/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS ROOM 104, 105, 106 EXCEPT PANEL WALL 1. RAPIDLY SUPPORT BOXES IN WALLS 2. SUPPORT SUPPORTS |
|
11/17/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TEMP RELOCATION OF TRANSFORMER "DP" 2) RECEIVED MONEY ORDER 08-596519755 FOR $108.00 |