Permit: T06CM02412

Parcel: 13323190A


Addresses:

7812 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM02412

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/17/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/12/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
06/20/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/15/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/14/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FLORAL: CAP PLUG STIP CONDUCTOR WITH AN APPROVED TERMINATION-NOT BLACK TAPE
2) CORDS NOT ALLOWED FOR PERMANENT WIRING METHODS 400.7
3) WHERE IS DISCONNECTING MEANS FOR ICE MACHINE
4) NEED PERMANENT CIRCUIT DIRECTORIES
5) BONDING JUMPER TO BE SIZED PER 250.122
6) CLEAN SURFACE UNDER GROUND BAR 250.12
7) TILES: OK ICREAM CASE TO COLUMN 4.0 AND COLUMN H BACK, OK FLOOR BOX CHICKEN WARMER-CONDUIT AND BOX AND OK CONNECTION SEAFOOD STEAMER
06/01/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CANS FROM SOFFIT
NO LIGHT LEAKS IN HOOD DUCT

1. BOXES IN SLAB COVERED WITHOUT INSPECTION
CANNOT BE USED UNTIL INSPECTED

RECEIVED MONEY ORDER #08-741555488 FOR $108.00
05/21/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/07/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/01/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/30/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TEMP DELI & BAKERY
OK END WALL FROZEN SEAFOOD
04/23/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/17/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SENSOR & SPLICES TO BE ACCESSIBLE

OK WALKER DUCT
OK HARD LID BATHROOMS EXCEPT AS NOTED
OK DEFROST CABINET LABELING
03/26/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK FLORAL WALL
2) OK W/P COVER NEW ROOF-OK TO USE
03/25/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/23/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/20/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/19/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/16/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS PHARMACY EXCEPT RADIUS
OK NEW LIGHTS SEAFOOD
OK TO USE NEW ROOF GFCI'S

1. SUPPORT M/C & FIXTURE WHIPS CORRECTLY

* W/P COVERS 406.8
03/15/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SUPPORT BOXES INSIDE OF UNITS.
2. TIGHTEN LOOSE FITTINGS.
3. PLEASE VERIFY IF BOX IS FOR BONDING AT 250V
OR MORE 250.97
4. FILL UNUSED OPENING
5. MAINTAIN WORKING CLEARANCE REMOTE HEADERS

OK TEMP DAIRY/DELI CASES TO ENERGIZE
OK TO CONNECT NEW FEEDERS TO RFA2
03/14/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/12/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/06/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/15/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/14/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/12/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/11/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TEMP POWER TO NEW SHELL

1. LABEL CIRCUIT DIRECTORIES
2. CUT TIES LOOSE FOR BUNDLING TO PREVENT HEATING OF CONDUCTORS.
3. PLEASE VERIFY DERATING OF CONDUCTORS IN GUTTER AND RACEWAYS.
4. ONLY ONE CONDUCTOR PER TERMINAL GROUND BAR IN GUTTER.
5. OPEN JUNCTION BOXES
6. SUPPORT CONDUIT AS PER CODE - 3' & 10"
7. VERIFY NUMBER OF CONDUCTORS PER WIRE NUT.
02/07/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) AREAS AND EQUIPMENT HAVE BEEN ENERGIZED WITHOUT INSPECTION-PLEASE DE-ENERGIZE UNTIL INSPECTED
02/01/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO PANELS PD1, P3, P3A, BD1 AND BP2 AS MARKED ON STICKERS
2) OK BREAKROOM WALLS
01/29/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
DISCUSSED SERVICE EQUIPMENT WITH CONTRACTOR
01/12/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/03/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. JUNCTION BOXES TO BE ACCESSIBLE
2. SCREWS AND NAILS TO BE PER 314.23 (B) (1)
3. SUPPORT CONDUITS

OK WALLS PRODUCE PREP
12/13/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS ROOM 104, 105, 106 EXCEPT PANEL WALL
1. RAPIDLY SUPPORT BOXES IN WALLS
2. SUPPORT SUPPORTS
11/17/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TEMP RELOCATION OF TRANSFORMER "DP"
2) RECEIVED MONEY ORDER 08-596519755 FOR $108.00