Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T06CM02412
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/17/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
07/06/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK PHARMACY OK PVC CONDUITS TO GENERATOR PAD OK 3/0 TO GROUND ROD 1. INSTALL GROUNDING FOR GENERATOR AS PER PLANS |
|
06/04/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK DELI TO DELI HOT CASE 3/4" PVC OK ALARM PANEL (CS) 1. SUPPORT WIRE FOR FIXTURE TO BE AS PER 300.11 2. PLEASE OPEN STRIP LIGHTING TO INSPECT - 2 PER ROW STAGGERED. |
|
06/01/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* OK 4 FLOOR BOXES & CONDUIT FOR SEASONAL AREA & LIQUOR OK SUSHI CASE OK SEAFOOD & MEAT COFFINS OK GFCI AT DELI 1. FINISH SUPPORTING VDV CABLING AS PER 725.6, 800.6, 300.11 TO BE ABLEL TO GET TILES --- DO NOT SET UNTIL COMPLETED IN AREAS RECEIVED MONEY ORDER #08-741555745 --- $108.00 |
|
05/15/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
04/26/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
04/20/2007 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
04/19/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. TIGHTEN LOOSE FITTING 2. SUPPORT FLEX CONDUIT AS PER CODES 12" & 4' 3. FINISH VDV ABOVE BUTCHER OK CORD DROP BUTCHER OK PVC CONDUIT EXTENSIONS MEAT & SUSHI CASES OK TEMP LIGHTING NEW AREA OK ICE CREAM CASES OK 5 WALL PACK NEW SECTION |
|
04/13/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
04/11/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
04/03/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
03/07/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
01/12/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK WALLS CBT OK 3 - 2" PVC CONDUIT TO WALKER DUCT IN ROOM NEW SCAN OK WALKER DUCT 1. USE PROPER SEAL FOR CONNECTOR AS DISCUSSED. |
|
12/11/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK 4 - 3" PVC BEHIND BUILDING |
|
11/17/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK 3 - 2 1/2" PVC CONDUIT AT SERVICE |
|
11/13/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 6 - 3" PVC AT DISTRIBUTION CENTER WEST (APPROX. 60') 1ST LAYER SCH. 40 PVC W/PVC 90 DEGREES |