Permit: T06CM02391

Parcel: 10707005K


Addresses:

1375 W GLENN ST 02


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T06CM02391

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
10/31/2008 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
60 POUND TEST ON GAS PIPING OK
GAS PIPING REPLACED WITH LISTED PIPE
10/28/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
10/16/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
ALL PIPING ABOVE CEILING HAS BEEN PAINTED
UNABLE TO DISCERN LISTING
UNLISTED PIPE NOT APPROVED
CONTINUED "NOT READY" WILL RESULT IN REINSPECTION FEE
10/08/2008 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXPOSE ALL PIPING ABOVE CEILING FOR INSPECTION
SEE NOTES FROM 7/10/08-9/5/08-9/10/08
2. GAS PIPING PAINTED BEFORE INSPECTION. NO PORTION OF ANY WORK MAY BE CONCEALED UNTIL IT HAS BEEN INSPECTED AND APPROVED. PAINTING COVERS THE LISTING.
3. SEE NOTE NUMBER 4 FROM 7/10/08
CONTRACTOR TO PAY REINSPECTION FEE