Permit: T06CM02391

Parcel: 10707005K


Addresses:

1375 W GLENN ST 02


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM02391

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/01/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
09/19/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
PROVIDE HISTORY FOR INSPECTION FOR CORRECTIONS
DATED 7/10/08 & 9/5/08

THIS INSPECTION FOR CLOSET FLANGES ONLY WHICH ARE OK
07/10/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. VENT SYSTEM INCOMPLETE
2. NO TEST ON ABS
3. ABS SHALL BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES, THEN NO MORE THAN FOUR FEET BETWEEN HANGERS
4. CONTINED "NOT READY" WILL RESULT IN REINSPECTION FEE
07/02/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER TO ABOVE CEILING
07/01/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SEWER PRE-CON OK
ADD SUPPORTS AS REQ'D
05/07/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CONTRACTOR TO ENSURE END OF THE LINE CLEANOUT IS THREE INCH. OK TO POUR PAD AROUND INTERCEPTOR.
04/28/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
4" ABS FROM TRENCH DRAIN TO SUMP #1 OK
OK TO COVER
04/23/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
TRENCH DRAIN THRU INTERCEPTOR NOT OK TO COVER
I HAVE NOT SEEN ANY PIPING ON THE DISCHARGE SIDE OF THE SUMP. PLANS CALLS FOR 6"