Permit: T06CM02391

Parcel: 10707005K


Addresses:

1375 W GLENN ST 02


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM02391

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/14/2009 ELECTRIC - FINAL Approved ALL ELECTRICAL INSPECTED BY D SANTACRUZ AND R HOLLANDER. FINAL APPROVAL OF DYNAMOMETERS PER LEERAY HANLY.
04/02/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
04/01/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
APPROVAL WILL BE SUBJECT TO CONVERSATION WITH SENIOR BLD. INSPECTOR - VERIFY APPROVAL OF DYNO VERIFICATION
01/09/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TO EXTEND TCO
OK DYNO 1-LINE DIAGRAM
OK FLAG POLE LIGHTS

1. NEED REVISED LUMEN CALC'S TO SHOW FLAGPOLE UP LIGHTING. ALSO, FLAGPOLE LIGHT FIXTURE NOT ON FIXTURE SCHEDULE
2. WAITING ON VERIFICATION OF LISTING FOR DYNO ASSEMBLY
11/25/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. A GROUNDING ELECTRODE SYSTEM IS NEEDED FOR DYNO TRANSFORMER
2. PLEASE VERIFY LISTING AND LABELING OF DYNO
3. NEED REVISED PLANS FOR DYNO TO MATCH WHAT IS INSTALLED
4. FINISH POLE LIGHT, FLAG POLE LIGHT AND NEED ACCESS FOR VDV CABLING
11/17/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BOND POLE PER 250.54
2. FINISH POLE
3. FINISH DYNO
4. FINISH PREVIOUS ITEMS
11/14/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BOND BUSHINGS PER 250.97
2. LABEL CONTROLLERS
3. USE WIRENUTS PER MANUFACTURES LISTINGS
4. FINISH VDV CABLING

*INTERIOR ONLY CHECK EXTERIOR NEXT TIME