Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM02391
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/14/2009 | ELECTRIC - INTERMEDIATE | Approved | ||
03/25/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* OK 1 - 4" FEEDER 1 - 1 1/4" FEEDER, 2 - 1" CONTROLS PVC WEST OF BUILDING |
|
01/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
10/13/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
10/07/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROTECT CONDUCTOR PER 252.46 & 300.4 2. LABEL EQUIPMENT 3. NEED ILLUMINATION AT EQUIPMENT TO BE ENERGIZED - 110.26 (D) 4. GROUND LUG TO BE ATTACHED TO ENCLOSURE 5. PLUG & SWITCH OR PLATE BOXES BELOW 8' |
|
07/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
06/27/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROVIDE LISTING THAT ALLOWS EMT & FITTINGS TO BE INSTALLED IN GROUTED WALLS - SEE NEC 300.6 THESE RACEWAYS WERE ALSO INSTALLED WITHOUT INSPECTION. 2. ENCLOSURES CONTAINING FIRE ALARM TERMINATIONS TO BE RED IN COLOR - NEC 760.10 OK WALL COVER LOWER LEVEL OFFICES & CUSTOMER SERVICE |