Permit: T06CM02359

Parcel: 141331510


Addresses:

8379 S EGYPTIAN DR


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM02359

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
01/04/2007 FRAMING Approved IVRS - Inspection :*
01/02/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 1, 2 & 5 NOT DONE
12/26/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CAULK ALL PENETRATIONS, AT EXT. LATHE
2) BROKEN FLOOR TRUSS GARAGE, NEED ENG. REPAIR
3) ADD A.B.'S AT FRONT SHEAR
4) DBL STUD FULL HT AT LTT20 STAIR NAIL TO SHEAR
5) WRONG HANGER AT GIRDER 2ND FLOOR
6) NAIL FLOOR AT STAIR
12/19/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO TRUSS BLOCKING 1ST FLOOR PER 2/D6
2. MISSING HD AT STAIRWAY SHEAR
3. SHIM ALL LET IN IF MORE THAN 1/2 REPLACE STUD
4. REPLACE INSTEAD 2X6 AT LAUNDRY ROOM
5. 2ND FLOOR EXT WALL NEEDS FLOOR NAILING - LOAD WINDOW WALL