Permit: T06CM02356

Parcel: 141331580


Addresses:

8368 S EGYPTIAN DR


Inspection Status: Approved

Inspection History: STUCCO MESH

Permit Number - T06CM02356

Inspection Description - STUCCO MESH

Inspection Status - Approved

Date Description Inspector Results Comments
12/28/2006 STUCCO MESH Approved IVRS - Inspection :*
12/19/2006 STUCCO MESH Not ready for Inspection IVRS - Inspection :*
1. LOOSE BOT. PLATE GARAGE/HOUSE DOOR
2. ELECT. BOX ATTACHED TO WALL LAUNDRY
3. ALL STUDS IN SHEAR WALLS THAT TIE TO P.A OR H.D'S O BE NAILED TO OSB SHEAR.
4. CS20 STRAP TO BE IN SAME VERTICAL LINE AS LTT20 BELOW AT STAIR.
5. NEED CORRECT PITCH ON KIT. VENT SINK
6. NEED BLKS. BEHIND THA HANGER STAIR HEADER
7. ROOF TRUSSES, TRUSS FRONT USE 16DS, MISSING NAILS WRONG SIZE HANGER.
8. BLK MECH. VENT S/W BED 2ND FLOOR, TORN GRADE "D" PAPER SAME ROOM
12/14/2006 STUCCO MESH Cancelled IVRS - RI canceled
11/29/2006 STUCCO MESH Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/20/2006 STUCCO MESH Not ready for Inspection IVRS - Inspection :*