Permit: T06CM02354

Parcel: 141312470

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM02354

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/21/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
07/20/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ITEM 03050 NOT REQUIRED/ALL ELECTRIC
2) PEX TO CLOSE TO LIGHT CANS
3) BLK ALL MECH DUCTS
4) RAISE HORIZONTAL 2 X 4 AT F/PLACE UP TO 32"
5) MISSING 3 STUDS 1ST AND 2ND FLOOR
6) WRONG NAILS AT H.D.STRAP
7) OK TO INSULATE