Permit: T06CM02354

Parcel: 141312470

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T06CM02354

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
08/25/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
06/22/2006 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) SPAULING AT GARAGE R4 NEED RETRO
2) OK TO COVER WITH LATHE
06/19/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FLOOR NOT NAILED, BLOCK ALL UN-SUPPORTED END JOINTS
2) ADD WIND BRACE SOUTH WALL
3) 2 8D'S AT 6" ON CENTER SHEAR 2ND FLOOR INTERIOR BETWEEN FLOOR TRUSSES NAIL BOTTOM UP
4) SPAULING AT FRONT STHD14-NEED RETRO (GARAGE)
5) NORTH WALL 2ND FLOOR BLOCK FOR BLOCKED SHEARWALL (GYP BOARD)
6) NO 8D NAILS IN ANY LOAD BEARING HANGER (GIRDER HANGER NEEDS 16D COMMON NAILS)
7) NORTH WALL 1ST AND 2ND FLOOR 18" LAP C20 COIL STRAPS
8) ON ROOF BLOCK UNDER OSB TURNED PARALLEL TRUSSES
9) BLOCK BETWEEN FLOORS AT GIRDER SUPPORTS FROM ABOVE