Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM02334
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/09/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/26/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* GIRLS TR 212 DWV OK EXPOSE FOAM PIPE WRAPS ON PIPING PENETRATING FLOOR |
|
04/19/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SOUTH OF COL. E OK TO COVER WALLS AND ABV CEILING CALL FOR CLOSET FLANGE INSP. WHEN READY. |
|
04/18/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RMS 117 AND 218 PIPING OK RM 217 OK TO COVER RMS 115 & 216 NR |
|
04/12/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSTALL HANGER ON HORIZONTAL PIPING, NOT 90 DEG. ON 1ST FLOOR VENT. PROPERLY INSTALL VENT ON FLOOR DRAIN, POINT OF VENT SHALL BE ABOVE FLOW LINE. RETEST WATER PIPING AT P-2 SHALL BE 1 1/4" PER PLAN HAMMER ARRESTOR REQUIRED |
|
04/09/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) WATER PIPING OVERHEAD HOSE BIBS, HOT AND RETURN, COLD FOR DOWN STAIRS COORIDOR AND RESTROOM (MENS) 1ST FLOOR AND HOT RETURN UP STAIRS MENS RESTROOM |
|
04/05/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* DWV BOYS TR UPSTAIRS OK-WATER NOT COMPLETE CORRECT SLOPE, PROVIDE SHADING AND INSTALL TRACER WIRE |
|
04/05/2007 | PLUMBING - INTERMEDIATE | Denied | TOILET RM #217 DRIP AT 2" 1/8" B DRIP AT C.O WATER PIPING NOT READY |
|
03/12/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 2" GAS SERVICE STUBBED IN, UP WALL AND CAPPED IN CEILING W/TEST. OK TO COVER WALL. USE 3050 FOR GAS PIPE INSP. USE 15PSI GAUGE FOR LOW PRESSURE TEST ALL HOSE BIB DROPS W/110 PSI TEST OK TO COVER |