Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM02334
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/13/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 10, 05, 35, 36, 61, 62, 75, 85, 99 |
|
07/11/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* PARTIAL INSPECTION ONLY CONTINUATION OF FINAL INSPECTION STARTING IN BOILER ROOM 1. CHILLER PUMP DISCONNECTS TO HAVE PROPER WORKING CLEARANCE, PROPER FUSE SIZES & IDENTIFICATION - NEC 110, 430 2. PROVIDE DISCONNECT FOR BOILER POWER -- NEC 422 2ND FLOOR ELECTRICAL ROOM 1. SECURE TRANSFORMER TO FLOOR, INSTALL ISO PADS NEC 110.3, 110.13 2. PANEL DIRECTORIES TO BE CORRECT, NEAT, LEGIBLE NEC 408.4 3. CHECK FUSE SIZES ELEVATOR DISC. 3. FINISH ALL LOW VOLTAGE WIRING 4. HAVE OVERFILLED J-BOXES ADD EXTENSIONS -- NEC 316.16 WILL LOOK @ CLASSROOMS, ROOFTOP, EXTERIOR NEXT INSPECTION, ALSO WILL TEST GENERATOR & EMER. CKT |
|
07/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY 1. EMERGENCY BRANCH CKTS TO BE FED BY 30 AMP PER PLAN (EN-1 PANEL) 2. PROPERLY IDENTIFY SAME CKTS IN PANEL EN-1 3. IDENTIFY FEEDER DISCONNECT BREAKER @ SES 4. AT SES EXTERIOR, STRAP EMT & INSTALL FEEDER J-BOX COVER SCREWS 5. AT ANNEX BOILER ROOM, DRIVE GROUND RODS SINCE UFER STOLEN 6. LABEL "MAIN DISCONNECT" FOR ANNEX IN BOILER ROOM 7. IDENTIFY ALL DISCONNECTS 8. GROUNDS #6 & SMALLER TO BE GREEN OR BARE ENTIRE LENGTH 9. BOND RACEWAYS OVER 250V WHERE CONCENTRICS OR ECENTRICS ARE ENCOUNTERED PARTIAL INSPECTION ONLY -- SES TO ANNEX BOILER ROOM |