Permit: T06CM02334

Parcel: 11107313A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM02334

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/13/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10, 05, 35, 36, 61, 62, 75, 85, 99
07/11/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
PARTIAL INSPECTION ONLY
CONTINUATION OF FINAL INSPECTION STARTING IN BOILER ROOM
1. CHILLER PUMP DISCONNECTS TO HAVE PROPER WORKING CLEARANCE, PROPER FUSE SIZES & IDENTIFICATION -
NEC 110, 430
2. PROVIDE DISCONNECT FOR BOILER POWER -- NEC 422

2ND FLOOR ELECTRICAL ROOM
1. SECURE TRANSFORMER TO FLOOR, INSTALL ISO PADS
NEC 110.3, 110.13
2. PANEL DIRECTORIES TO BE CORRECT, NEAT, LEGIBLE
NEC 408.4
3. CHECK FUSE SIZES ELEVATOR DISC.
3. FINISH ALL LOW VOLTAGE WIRING
4. HAVE OVERFILLED J-BOXES ADD EXTENSIONS -- NEC 316.16

WILL LOOK @ CLASSROOMS, ROOFTOP, EXTERIOR NEXT INSPECTION, ALSO WILL TEST GENERATOR & EMER. CKT
07/02/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY
1. EMERGENCY BRANCH CKTS TO BE FED BY 30 AMP PER PLAN
(EN-1 PANEL)
2. PROPERLY IDENTIFY SAME CKTS IN PANEL EN-1
3. IDENTIFY FEEDER DISCONNECT BREAKER @ SES
4. AT SES EXTERIOR, STRAP EMT & INSTALL FEEDER J-BOX COVER SCREWS
5. AT ANNEX BOILER ROOM, DRIVE GROUND RODS SINCE UFER STOLEN
6. LABEL "MAIN DISCONNECT" FOR ANNEX IN BOILER ROOM
7. IDENTIFY ALL DISCONNECTS
8. GROUNDS #6 & SMALLER TO BE GREEN OR BARE ENTIRE LENGTH
9. BOND RACEWAYS OVER 250V WHERE CONCENTRICS OR ECENTRICS ARE ENCOUNTERED

PARTIAL INSPECTION ONLY -- SES TO ANNEX BOILER ROOM