Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM02326
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/16/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/11/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. SCREW CLOSET FLANGES TO THE FLOOR 2. YARDWATER OK |
|
07/17/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NEED TO SEE CLOSET FLANGES OK TO COVER ALL AREAS |
|
07/12/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CONTINUED "NOT READY'S" MAY RESULT IN A REINSPECTION FEE |
|
07/11/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES. NO MORE THAN FOUR FEET BETWEEN HANGERS. 2. FILL TUBS ALL THE WAY UP. 3. INSPECTION STOPPED. |
|
07/10/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
07/05/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PLEASE POST YOUR ADDRESS 2) WATER TEST OK 3) HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP 4) SUPPORT VERTICAL PIPE SUPPORT OVERHEAD PIPE 5) FILL TABS 6) PLUMBERS TAPE NOT APPROVED 7) USE SWEEPS ON RE-VENT BELOW 42" |