Permit: T06CM02317

Parcel: 116262560


Addresses:

2650 W CALLE PUEBLA

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/08/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/05/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
REMOVE NEUTRAL BOND SCREW AT SUB-PANEL

OK PREVIOUS ITEMS
11/30/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEPARATE GROUNDS AND NUETRALS AT SUB-PANEL
2. SPA CONDUCTORS TO BE GFCI PROTECTED AND IN SEPARATE RACEWAY 680
3. PLANS CALL FOR #8 GROUND PV DISCONNECT TO INVERTER WE HAVE #10
4. CHASE NIPPLE NOT AN APPROVED FITTING.
5. CORRECTLY INSTALL GROUNDING CONDUCTOR AT MODULES
6. SUPPORT JUNCTION BOXES.