Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 01/09/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIRESTOP ARCH WAY KITCHEN 2) MISSING TRUSS BLOCKING PER 2/D2 1ST FLOOR 3) NOT COMPLETE AT ROOF VENTS 4) LOAD WINDOW MISSING 5) UNTIL GARAGE ROOF INSULATION IS UNCOVERED 6) FLOW RESTRICTION DUCT KITCHEN 7) INSULATION BEHIND TUB/SHOWER MISSING 8) EXT. WALL ON 2ND FLOOR NEED MORE PLATE NAILING 9) FIRESTOP CHASE MASTER BEDROOM CLOSET 10) NEED TO UNCOVER INSULATION IN GARAGE ROOF TO FINISH INSPECTION 11) MISSING MTT28 STRAP AT SHEAR PANEL FAMILY ROOM- NOT COIL STRAP |
|
| 01/08/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO REMOVE INSULATION SO I CAN HAVE A VISUAL ON ALL WALLS FOR ELECTRIC, PLUMBING, ETC... |