Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM02292
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/19/2007 | FRAMING | Approved | IVRS - Inspection :* | |
01/09/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NAILING ON SHEAR TRANSFER NOT PER 5/D3 2) SHIM 2 X 12 HEADERS 3) NO ELECTRIC RISER FOR PANEL 4) NO DWV TEST 5) PEX LINES IN KITCHEN, MOVE ABOVE BOTTOM TRUSS CHORD 6) TIGHTEN ALL LOOSE ANCHOR BOLTS 7) MASTER BATH SHOWER NEEDS BLOCKING ON EDGE OF SHOWER 8) NEED TO BLOCK DUCT VENT HALL BATHROOM 9) FIRESTOP CHASE AT HALLWAY BATH |