Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM02289
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/16/2007 | FRAMING | Approved | IVRS - Inspection :* 1) THERE WAS A 3' X 4' APPROX. SECTION FO CONCRETE, SAW CUT TO MAKE REPAIRS ON ABS 2" BRANCH-POST TENSION CABLES NOT TORN 2) DOWNSTAIRS BATHROOM: WILL NEED A COMPACTION TEST DONE BY A SPECIAL INSPECTION, WITH DOCUMENTATION-WILL CHECK AT NEXT INSPECTION |
|
01/12/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIX LET-INS 2) NEED TO FIX LEAK AT BATH TUB 3) REPAIR PIPE UNDER CONCRETE 4) NO DWV TEST |
|
01/05/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) H.D. AT STAIRWAY IN WRONG LCATION 2) 2ND FLOOR LET INS NEED TO BE SHIMED NOT GLUED 3) PEX LINES IN KITCHEN NEED TO BE ROUTED 4) LEAK AT BATHTUB DOWNSTAIRS 5) NO DWV TEST |
|
12/18/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BLK AT COMBUSTION AIR VENTS 2) SHIM LETINS ALL WALLS 3) MISSING H.D. AT STAIRWAY SHEARWALL 4) LOAD WINDOW NOT INSTALLED 5) DOWNSTAIRS BATH-NEED PROTECTION ON DRAIN AT CEILING FROM 2ND FLOOR 6) GAS LINE TO STOVE NEEDS TO BE SECURED IN WALL 7) NO PRESSURE READING ON GAUGE 8) A/C VENT TO MASTER BATH HAS RESTRICTION 9) BLOCK MECHANICAL BOOT IN BEDROOM AND LOFT 10) PEX LINE OVER KITCHEN SINK, NEEDS TO BE MOVED AWAY FROM CAN LIGHT 11) NO WATER PRESSURE 12) NO DWV TEST |