Permit: T06CM02287

Parcel: 141331830


Addresses:

8352 S GUPTA DR


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T06CM02287

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
08/01/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
2, 3 & 4 NOT DONE
07/25/2006 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) NO PERMIT ON SITE
2) REMOVE SHIMS AT NON-BEARING 3 PT AT REAR
3) NEED X BRACE TRUSS FRONT
4) CABIN TIE OR STRAP TOP PLATES AT MASTER BATH
07/17/2006 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) OK TO DRY IN ROOF AND WALLS
2) FIX NOTCH IN TOP CHORD, 24 FROM HEEL JOINT
3) X BRACE TRUSSES FRONT BACK
3) SHIM ALL B/PTS
07/12/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CHECK SHEAR NAILING 2 X MEMBERS CAN'T HAVE NAILING PATTERNS CLOSER THAN 2"
2) A35 AT TOP PLATES MUST BE TIGHT
3) CHECK ROOF NAILING ON SOUTH SIDE
4) CLIP LEDGER IN GARAGE AND ENTRY PER 10A/D2
5) HINGE BRACES AT GABLE ENDS 6' ON CENTER
6) REPAIR TRUSSES NOTCHED 2' FROM HEEL-DON'T OVER PENETRATE NAILS
7) SHEAR MISSING AT S.E. CORNER