Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/21/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CALL THIS IN WITH PAINT BOOTH FINAL |
|
| 03/14/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* OK TO OCCUPY AREAS OF BUILDING COVERED UNDER THIS PERMIT ONLY. PAINT BOOTH AREAS NEED SEPARATE PERMIT AND INSPECTION AND ARE NOT TO BE OCCUPIED BEFORE APPROVAL. MAIN AREA STILL SUBJECT TO FINAL INSPECTION AND APPROVAL. |
|
| 03/13/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEED PERMIT AND INSPECTION FOR PAINT BOOTH AND ASSOCIATED ROOMS AND EQUIPMENT. 2. WIRING NOT COMPLETE 3. PROVIDE CORROSION PROTECTION FOR RACEWAYS AS REQUIRED IN CARWASH, ETC. |
|
| 03/12/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FINISH ALL WIRING FINISH PAINT BOOTH |
|
| 03/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR ROOFTOP ONLY 1. INSURE ELECTRICAL CONTINUITY OF RACEWAYS NEC 250.97 2. RACEWAYS INTO ROOFTOP UNITS TO BE COMPLETE INTO J-BOXES FOR POWER AND SERVICE RECEPTACLES NEC 300.10, 300.18, 300.12 |
|