Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM02274
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/07/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/06/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. EMERGENCY LIGHTING NOT WORKING. 2. CORRECTLY IDENTIFY PANEL DIRECTORY'S |
|
06/05/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. EMERGENCY LIGHTING IS NOT PER PLAN AND NOT ALL WORKING. 2. PANEL DIRECTORIES ARE NOT MARKED CORRECTLY. 3. SOME BREAKERS ARE NOT SEATED PROPERLY IN PANELS. 4. HAVE WRONG SIZE FUSES ON INSTA-HOT AND STRAP MC TO J-BOX. 5. HAVE ALL PANELS OPEN FOR INSPECTION. 6. CONDUCTORS IN RACEWAYS NEED TO BE PROPERLY DERATED NEC 310.15 7. THERE ARE RECEPTS ON THE PLAN THAT ARE NOT INSTALLED. 8. TIGHTEN ALL DEVICES SO THEY ARE FLUSH TO WALL AND NOT LOOSE. |