Permit: T06CM02274

Parcel: 108214430

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM02274

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/07/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/06/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. EMERGENCY LIGHTING NOT WORKING.
2. CORRECTLY IDENTIFY PANEL DIRECTORY'S
06/05/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. EMERGENCY LIGHTING IS NOT PER PLAN AND NOT ALL WORKING.
2. PANEL DIRECTORIES ARE NOT MARKED CORRECTLY.
3. SOME BREAKERS ARE NOT SEATED PROPERLY IN PANELS.
4. HAVE WRONG SIZE FUSES ON INSTA-HOT AND STRAP MC TO J-BOX.
5. HAVE ALL PANELS OPEN FOR INSPECTION.
6. CONDUCTORS IN RACEWAYS NEED TO BE PROPERLY DERATED NEC 310.15
7. THERE ARE RECEPTS ON THE PLAN THAT ARE NOT INSTALLED.
8. TIGHTEN ALL DEVICES SO THEY ARE FLUSH TO WALL AND NOT LOOSE.