Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/07/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/31/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SUPPORT EXISTING VDV CABLEING PER 725.6 & 800.6 2. MAINTENANCE WORKING CLEARANCE AT ELECTRICAL SERVICE AT ALL TIMES. 3. CONDUCTOR TO BE PROTECTED PER TAP RULES 240.21 |
|
| 08/24/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. OPEN CEILING TILES FOR INSPECTION - NO ABOVE CEILING INSPECTION HAS BEEN DONE. 2. ABOVE WALK IN BOX NOT COMPLETE 3. WHERE ARE ROOF DISCONNECTS FOR ICE MAKER 4. TIGHTEN LOOSE ROOF FITTINGS 5. MAINTAIN WORKING CLEARANCES AT ELECTRICAL EQUIPMENT AT ALL TIMES. 6. OK FOR DISCONNECTS ON ROOF FOR SINGLE SYSTEM OF REFRIGERATION WALLS. 7. CHECK POWER SOURCES FOR SIGNS AT SODA COUNTER. *CONTRACTOR IS AWARE OF LIABILITIES OF OCCUPYING UNFINISHED AREAS WITHOUT INSPECTION CLEARANCES. |
|
| 07/14/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK COFFEE BAR & SODA COUNTER 1. SEALS FOR WALK-IN BOX TO BE NON-COMBUSTIBLE 300.7 2. WE HAVE OVERFILL AT BOX TOP OF WALK-IN |
|
| 07/13/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLEASE VERIFY LISTING LABELS FOR GRINDER, CREAMER MACHINES. 2. MAINTAIN WORKING CLEARANCES IN FRONT OF ELECTRIC PANEL AT ALL TIMES 110.26 3. PROVIDE ACCESS TO TOP OF WALK IN BOX TO INSPECT *BOXES TO BE AS PER 300.7 DO NOT USE UNLISTED EQUIPMENT. WALK IN BOXES HAVE NOT BEEN CLEARED FOR USAGE. *NOTE ABOVE CEILING TO HAVE VDV CABELING AS PER 725.3 & 6, 800.3 & 6 OK BACK COUNTER |