Permit: T06CM02273

Parcel: 13318007F


Addresses:

7022 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/07/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/31/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SUPPORT EXISTING VDV CABLEING PER 725.6 & 800.6
2. MAINTENANCE WORKING CLEARANCE AT ELECTRICAL SERVICE AT ALL TIMES.
3. CONDUCTOR TO BE PROTECTED PER TAP RULES 240.21
08/24/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. OPEN CEILING TILES FOR INSPECTION - NO ABOVE CEILING INSPECTION HAS BEEN DONE.
2. ABOVE WALK IN BOX NOT COMPLETE
3. WHERE ARE ROOF DISCONNECTS FOR ICE MAKER
4. TIGHTEN LOOSE ROOF FITTINGS
5. MAINTAIN WORKING CLEARANCES AT ELECTRICAL EQUIPMENT AT ALL TIMES.
6. OK FOR DISCONNECTS ON ROOF FOR SINGLE SYSTEM OF REFRIGERATION WALLS.
7. CHECK POWER SOURCES FOR SIGNS AT SODA COUNTER.

*CONTRACTOR IS AWARE OF LIABILITIES OF OCCUPYING UNFINISHED AREAS WITHOUT INSPECTION CLEARANCES.
07/14/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK COFFEE BAR & SODA COUNTER
1. SEALS FOR WALK-IN BOX TO BE NON-COMBUSTIBLE 300.7
2. WE HAVE OVERFILL AT BOX TOP OF WALK-IN
07/13/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLEASE VERIFY LISTING LABELS FOR GRINDER, CREAMER MACHINES.
2. MAINTAIN WORKING CLEARANCES IN FRONT OF ELECTRIC PANEL AT ALL TIMES 110.26
3. PROVIDE ACCESS TO TOP OF WALK IN BOX TO INSPECT *BOXES TO BE AS PER 300.7
DO NOT USE UNLISTED EQUIPMENT. WALK IN BOXES HAVE NOT BEEN CLEARED FOR USAGE.
*NOTE ABOVE CEILING TO HAVE VDV CABELING
AS PER 725.3 & 6, 800.3 & 6
OK BACK COUNTER