Permit: T06CM02272

Parcel: 11303040D


Addresses:

3800 N 1ST AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/31/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK FINAL
05/18/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. IDENTIFY DISCONNECTS AS "SERVICE DISCONNECTS"
NEC. 230.70
2. ENCLOSURE COVER FOR "AC 2" NEEDS TO BE ABLE TO OPEN TO A MINIMUM OF 90 DEGREES. NEC 110
3. NEED TO BOND NEUTRAL TO DISCONNECT ENCLOSURES.
NEC 250.24 (B)