Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/31/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL |
|
| 05/18/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. IDENTIFY DISCONNECTS AS "SERVICE DISCONNECTS" NEC. 230.70 2. ENCLOSURE COVER FOR "AC 2" NEEDS TO BE ABLE TO OPEN TO A MINIMUM OF 90 DEGREES. NEC 110 3. NEED TO BOND NEUTRAL TO DISCONNECT ENCLOSURES. NEC 250.24 (B) |