Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T06CM02257
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/11/2006 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* OK FOR SHEETROCK |
|
12/06/2006 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 3RD FLR. CONDENSATE DRAIN (FRONT OF ELEVATOR CHASE) AT PVC 3/4" TEE THIS COND. LINE IS BLOCKING/CRIMPING SUPPLY DUCT. REWORK CRIMPED AREA |
|
11/15/2006 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* - 1ST FLOOR 10" DUCT KINKED AT PENETRATION. - PROVIDE SCREWS IN EXHAUST DUCT CONNECTIONS. - 3RD FLOOR CONDENSATE DRAIN RUNS UPHILL & SUPPORT EVERY 4' HORIZONTAL SECTIONS. - PROVIDE BACKING AROUND ALL CEILING BOXES. |