Permit: T06CM02257

Parcel: 108251960

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T06CM02257

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/11/2006 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
OK FOR SHEETROCK
12/06/2006 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
3RD FLR. CONDENSATE DRAIN (FRONT OF ELEVATOR CHASE) AT PVC 3/4" TEE

THIS COND. LINE IS BLOCKING/CRIMPING SUPPLY DUCT.
REWORK CRIMPED AREA
11/15/2006 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- 1ST FLOOR 10" DUCT KINKED AT PENETRATION.
- PROVIDE SCREWS IN EXHAUST DUCT CONNECTIONS.
- 3RD FLOOR CONDENSATE DRAIN RUNS UPHILL & SUPPORT EVERY 4' HORIZONTAL SECTIONS.
- PROVIDE BACKING AROUND ALL CEILING BOXES.