Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2007 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 03/08/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* GROUND RODS TO BE 6' APART MINIMUM NEC 250.56, NEC 250.53 B NEED TO PAY REINSPECTION FEE |
|
| 03/06/2007 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* WORK NOT READY |