Permit: T06CM02256

Parcel: 108251970

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM02256

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/21/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
OK TO COVER ALL AREAS
11/15/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. ALL UNITS WILL HAVE THEIR NUMBERS CLEARLY AND VISIBLY POSTED!
2. ABS SHALL BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES. THEN NO MORE THAN FOUR FEET BETWEEN HANGERS.
3. REQUIRE 18" OF COPPER BEFORE TRANSITION TO PEX AT WATER SERVICE.
4. REQUIRE STAINLESS STEEL OR BRASS SCREWS AT CLOSET FLANGES.
5. BACK PITCHED VENTS NOT APPROVED.
11/14/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. 301.1.1 2003 UPC "ALL PIPE, PIPE FITTINGS, TRAPS, FIXTURES, MATERIAL AND DEVICES USED IN A PLUMBING SYSTEM SHALL BE LISTED OR LABELED BY A LISTING AGENCY".
2. 301.1.1 2003 UPC "EACH LENGTH OF PIPE AND EACH PIPE FITTING, TRAP, FIXTURE, MATERIAL AND DEVICE USED IN A PLUMBING SYSTEM SHALL HAVE CAST, STAMPED OR INDELIBLY MARKED ON IT THE MANUFACTURER'S MARK OR NAME WHICH SHALL READILY IDENTIFY THE MANUFACTURER TO THE END USER OF THE PRODUCT..."
3. PLEASE PROVIDE THE LISTING FOR THIS PRODUCT.