Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM02256
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/21/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* OK TO COVER ALL AREAS |
|
11/15/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. ALL UNITS WILL HAVE THEIR NUMBERS CLEARLY AND VISIBLY POSTED! 2. ABS SHALL BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES. THEN NO MORE THAN FOUR FEET BETWEEN HANGERS. 3. REQUIRE 18" OF COPPER BEFORE TRANSITION TO PEX AT WATER SERVICE. 4. REQUIRE STAINLESS STEEL OR BRASS SCREWS AT CLOSET FLANGES. 5. BACK PITCHED VENTS NOT APPROVED. |
|
11/14/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. 301.1.1 2003 UPC "ALL PIPE, PIPE FITTINGS, TRAPS, FIXTURES, MATERIAL AND DEVICES USED IN A PLUMBING SYSTEM SHALL BE LISTED OR LABELED BY A LISTING AGENCY". 2. 301.1.1 2003 UPC "EACH LENGTH OF PIPE AND EACH PIPE FITTING, TRAP, FIXTURE, MATERIAL AND DEVICE USED IN A PLUMBING SYSTEM SHALL HAVE CAST, STAMPED OR INDELIBLY MARKED ON IT THE MANUFACTURER'S MARK OR NAME WHICH SHALL READILY IDENTIFY THE MANUFACTURER TO THE END USER OF THE PRODUCT..." 3. PLEASE PROVIDE THE LISTING FOR THIS PRODUCT. |