Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/03/2007 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* HUB BLANK SCREWS STILL NOT INSTALLED TOP OF SERVICE |
|
| 03/21/2007 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) GROUND RODS DRIVEN 2) NOTE: INSTALL HUB BLANK SCREWS-ASAP |
|
| 03/08/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* GROUND RODS TO CLOSE TOGETHER NEED 6' MINIMUM NEC 250.56, NEC 250.53 B |
|
| 03/06/2007 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* WORK NOT READY |