Permit: T06CM02254

Parcel: 108251990

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM02254

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/10/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
FOR FUTURE INSPECTIONS
1. ALL DRAINAGE PIPING INCLUDING TRAP ARMS REQUIRE A MIN OF 1/4" PER FOOT SLOPE
2. VENT TAKE OFFS SHALL BE AT A MIN. OF 45 DEG.
07/06/2007 PLUMBING - FINAL Cancelled
07/05/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
KIT SINK; POINT OF VENT SHALL BE ABOVE FLOW LINE
ROLL WYE UP TO MIN 45 DEG.
CABANA; HW AND CW CROSSED
-- CLEANOUT PLUG SHALL BE FACTORY TAPPED TO RECEIVE SCREW
07/03/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
07/02/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
- INSULATE HWR
- INSTALL PROPER DRAINAGE FITTING FOR AAV
A SANTEE IS FOR VERTICAL INSTALLATION ONLY.
- CHINA BOWL CAPS. CAULK WC AT FLOOR.
- PROVIDE ACCESS AT MIXING VALVES IN LAUNDRY OR REMOVE -- TRIM C.O'S
- SET TUB FILL TUB W/WATER. HB VAC ON ROOF
CABANA SINK
06/05/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
SHOWER PAN LINERS OK
PERM CAPS FIRST FLOOR OK
05/30/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SHOWER PANS INSPECTION
2. WATER TEST IS DOWN. TEST TO FLOOD LEVEL 412.8.2
3. LINING MATERIAL MUST EXTEND OUTWARD OVER TOP OF ROUGH THRESHOLD AND BE TURNED OVER AND FASTENED ON THE OUTSIDE FACE -- SEC 412.8
4. LINING HAS BEEN CUT
5. NAILING TO BE A MIN OF 1" ABV THRESHOLD
6. IF DELETING 1ST FLOOR BATHROOM, CALL FOR INSPECTION OF PERM CAPS IN WALL AND BELOW FLOOR.
7. CALL TO INSPECT GARDEN TUBS.